top of page
Search

Two Smaller Backflows Instead of One Big One — Testing Without Shutting Off the Water

nashbrienza
Nov 9
1 min read

Why two smaller backflows instead of one big one?


This is a 3-inch water service at a retirement home, protected by two 2-inch backflow preventers installed in parallel instead of one large device.


Here is the reason: in a home like this, the water simply cannot be shut off. Residents depend on it around the clock for drinking, bathing, and medical care. Testing a backflow preventer means isolating it and closing its valves — on a single large device, that means shutting down the water to the entire building.


With two devices in parallel, we isolate and test one while the other stays in service and keeps the building supplied. Then we switch and test the second one. The annual testing gets done, the protection never lapses, and the residents never lose their water.


Two 2-inch devices in parallel also handle the flow of the 3-inch service, and down the road, if one ever needs repair, the building still is not left without water.


Parallel installation: the smart setup wherever the water has to stay on.


Van Horne Plumbing and Backflow tests backflow preventers across the GTA. If your building cannot be shut down for testing — retirement homes, clinics, condos, and other occupied buildings — we can help you plan around it.

 
 
 