Two Smaller Backflows Instead of One Big One — Testing Without Shutting Off the Water
Why two smaller backflows instead of one big one? This is a 3-inch water service at a retirement home, protected by two 2-inch backflow preventers installed in parallel instead of one large device. Here is the reason: in a home like this, the water simply cannot be shut off. Residents depend on it around the clock for drinking, bathing, and medical care. Testing a backflow preventer means isolating it and closing its valves — on a single large device, that means shutting down
nashbrienza
4 hours ago1 min read


Vertical Installs Save Time, Money, and Room — With the Right Device
A vertical install can save time, money, and room — if it's the right device. Run a backflow preventer straight up a riser like this one and you skip the offsets and extra fittings a horizontal run needs. Fewer fittings, less pipe, less labour — and in a tight mechanical room, the wall space it frees up matters. But here's the catch: not every backflow preventer is approved for vertical installation. Some models are horizontal-only — install one vertically and it can't be cer
nashbrienza
1 day ago1 min read


Premise Isolation Comes First
Premise isolation comes first. The premise isolation backflow preventer goes in immediately downstream of the water meter — upstream of every other connection in the building. Nothing ties in ahead of it. This mechanical room shows why the order matters: the irrigation line branches off downstream of the premise device, so it's protected too. One device at the entry point separates everything inside the building from the city's water supply. If a line ties in ahead of that de
nashbrienza
2 days ago1 min read


Spot the Problem: A Bypass Around a Backflow Preventer
Spot the problem with this install? We didn't install this one — we were called in to test it. Follow the copper loop running around the backflow preventer: that's a bypass. Open those valves and water flows straight past the device, completely unprotected. A bypass around a backflow preventer defeats the entire purpose of having one. The only place a bypass is permitted is upstream of the device — never around it. A backflow preventer only protects the water supply if all th
nashbrienza
3 days ago1 min read


Why Reviews Matter
Why do reviews matter? For a small, family-run business like ours, they matter a lot. When someone is looking for a backflow tester they can trust, a real review from a real customer is often what helps them decide. It also tells the true story of the work better than any ad could. If we've tested your backflow preventer, we'd be grateful if you shared your experience — it only takes a minute: https://g.page/r/CaEVYP97sJhPEBE/review Thank you for supporting a local family bus
nashbrienza
3 days ago1 min read


You Need a Pro to See Things Like This
Surveys find things like this all the time. This is an electronic trap primer. It drips water into floor drains so the traps don't dry out and let sewer gas into the building. The little brass device on the line is a dual check valve, and it's there to protect the drinking water. Except it doesn't count. A trap primer connects the potable water system to the drainage system, and the standard calls for an atmospheric vacuum breaker or an air gap. A dual check is non-testable a
nashbrienza
5 days ago1 min read


Lock In Your Rate: 3 & 5 Year Backflow Testing Agreements
Your backflow testing bill goes up every year. This stops that. Annual testing isn't optional — your city requires it, every single year. And like everything else, the price keeps climbing. Sign a 3 or 5 year testing agreement with Van Horne Plumbing and Backflow, and your per-device rate is locked in for the whole term. The more devices your building has, the more that lock saves you. No surprise increases. No scrambling when the city letter lands. We book it, test it, file
nashbrienza
5 days ago1 min read


An Honest Call: The Backflow That Never Needed to Be There
An honest call on a job today. This is a 1-inch backflow preventer feeding an eyewash station. The eyewash only needs a half-inch supply — this device was already here, meant for something else, and the eyewash just got hooked up to it. It's been tested every year since. And today, it failed. The easy money would be to repair it, retest it, and bill for both. But an eyewash station doesn't need a backflow of this caliber at all — so I told the client the opposite: remove it,
nashbrienza
6 days ago1 min read


Installed the Wrong Way: Why a Backflow Preventer's Nameplate Matters
This is why the nameplate matters. We were on site to test three reduced pressure backflow preventers, and all three were installed vertically. The problem: they're Zurn Wilkins 375AST assemblies, and the nameplate right on the device says 'For Horizontal Installation Only.' That's not a suggestion. A device installed outside its approved orientation isn't installed to the manufacturer's instructions — and if we tested it and signed off on it as compliant, we'd be putting our
nashbrienza
6 days ago1 min read


Sometimes This Is the Only Place It Can Go
Sometimes this is the only place it can go. No mechanical room, no spare wall — so this one lives under the washroom sink. Same rules as any install: accessible, testable, and protecting the building's drinking water every day. Tight space doesn't change the standard.
nashbrienza
7 days ago1 min read


Premise Isolation Install: Proper Supports Are Key
Premise isolation protects a building's whole water supply at the point it enters, with a backflow preventer. In this install, the device is a reduced pressure backflow preventer. The part that gets overlooked is the supports. This thing is heavy, and it's full of water. Without proper supports, all that weight hangs on the device and the joints — and over time you get sagging, stressed connections, and leaks, and a device that doesn't test right. Here the piping is supported
nashbrienza
Oct 281 min read


Premise Backflow Install: Make Sure Irrigation Is Downstream of the Device
Here's a detail that gets missed on a lot of installs: where the irrigation line ties in. On a premise backflow install, the device protects everything downstream of it — the whole building. That only works if every water use, including irrigation, is actually downstream of the device. If the irrigation line branches off before the premise preventer, that water has no protection at all. And irrigation is one of the higher-risk uses in a building. Fertilizer and chemicals sit
nashbrienza
Oct 261 min read


The Expansion Tank Nobody Checks — Until It Fails
Every commercial building with a backflow preventer is a closed system. When water heats up, it expands — and it needs somewhere to go. That somewhere is the expansion tank. It's also the part of the system nobody ever looks at. An expansion tank doesn't fail loudly. The internal bladder gives out, the tank fills with water and stops doing its job, and from the outside everything looks fine. Meanwhile the building lives with pressure spikes, relief valves that dribble or dump
nashbrienza
Oct 211 min read


Introducing the Van Horne Client Portal
We're excited to announce the launch of our new Client Portal at portal.vanhorneplumbing.com. Managing backflow compliance across multiple buildings means keeping track of a lot of paperwork — test reports, due dates, repair records. Our portal puts all of that in one place, available to you 24/7. With your client login, you can: - Download PDF copies of every backflow test report for your buildings - See at a glance when each device is due for its annual test - Request servi
nashbrienza
Oct 151 min read


One Device Guarding Nearly 30 Water Lines: Annual Backflow Test
Here's a look at a recent annual backflow test. This single backflow preventer sits upstream of an entire PEX manifold — nearly 30 individual home runs, every one of them carrying potable water downstream of this device. That's what makes the annual test non-negotiable. Check valves stand between the building's water supply and potential backflow contamination. We verify each one with a digital Mako test gauge, tag the device, and document the results. If your building has a
nashbrienza
Oct 121 min read


Why Does the City Require a Backflow Preventer on Your Water Main?
If you've ever received a letter from the city about backflow testing and wondered why they care so much about one device on your water main, here's the short answer: water can flow backwards — and when it does, it can put a whole neighbourhood's drinking water at risk. Your water main is a two-way street. Clean water flows from the city main into your building. But under the right conditions, that flow can reverse. There are two ways this happens: Backsiphonage is when press
nashbrienza
Oct 92 min read