Installed the Wrong Way: Why a Backflow Preventer's Nameplate Matters

nashbrienza
Nov 3
1 min read




This is why the nameplate matters.


We were on site to test three reduced pressure backflow preventers, and all three were installed vertically. The problem: they're Zurn Wilkins 375AST assemblies, and the nameplate right on the device says 'For Horizontal Installation Only.'


That's not a suggestion. A device installed outside its approved orientation isn't installed to the manufacturer's instructions — and if we tested it and signed off on it as compliant, we'd be putting our name on an installation that doesn't meet the requirements. That's liability we won't take on, and protection the building doesn't actually have.We confirmed it with Zurn directly: this model cannot be installed vertically. So instead of a pass, all three were recorded as a deficiency. The fix is to re-pipe them horizontally, or replace them with a model that's approved for vertical installation — then we test them and certify them properly.


The lesson for property managers and contractors: check the nameplate for the approved orientation before a device goes in. Not every model can be installed every way.