You Need a Pro to See Things Like This

Surveys find things like this all the time.
This is an electronic trap primer. It drips water into floor drains so the traps don't dry out and let sewer gas into the building. The little brass device on the line is a dual check valve, and it's there to protect the drinking water.
Except it doesn't count. A trap primer connects the potable water system to the drainage system, and the standard calls for an atmospheric vacuum breaker or an air gap. A dual check is non-testable and rated for minor hazards only — it's simply not approved for this application.
Nobody would ever spot this without going looking. That's exactly what a cross-connection survey is for: finding the deficiencies hiding in mechanical rooms before they turn into a contamination problem.
The fix here is straightforward — an AVB in place of the dual check, and it's compliant.
You need a pro to see things like this.
Van Horne Plumbing and Backflow provides backflow testing, repairs, and cross-connection surveys across the GTA. If your building has never had a survey, this is the kind of thing that's waiting to be found.